These fuses are recommended for AC power distribution system mains, feeders and branch circuits having inductive loads motors, transformers or non inductive loads lighting, heating where the available short circuit current does not exceed 200,000 RMS symmetrical amp. These dual element, time delay fuses have minimum industry standard time delay of 10 sec at 5 times the fuse rating 8 sec minimum for 250 V, 30 A and less. The time delay characteristics of these fuses typically allows them to be sized closer to the running ampacity of inductive loads to reduce cost and provide improved over current protection. These fuses will override normal equipment current surges to reduce unnecessary fuse openings. They are the most popular fuses used in the industry and the most economical for most applications, especially motors and transformers. They have moderate current limitation.
Bussmann Time Delay Fuse, Series: ECSR Series, 600 VAC, 25 A, Class: RK5, 200 kA Interrupt, 10 s Response, Dual, Ferrule Terminal, 5 in Length, 0.81 in Dia
Amperage Rating | : | 25 A |
Class | : | RK5 |
Diameter | : | 0.81 in |
Element Type | : | Dual |
Interrupt Rating | : | 200 kA |
Length | : | 5 in |
Response Time | : | 10 s |
Series | : | ECSR Series |
Terminal Type | : | Ferrule |
Voltage Rating | : | 600 VAC |
Bussmann ECSR-25